Data Center Water Use Calculator

Estimate daily and yearly cooling water from IT load and WUE, in liters and gallons.

Interactive calculator

Estimate cooling water use

–Gallons per day
–Liters per day
–Gallons per year
–Households' daily home use

WUE (water usage effectiveness, from The Green Grid) = site water used for cooling and humidity ÷ IT energy. Closed-loop and dry-cooled sites can run near zero; evaporative cooling in hot, dry weather uses far more. This counts on-site water only, not the water used to generate the electricity. The household comparison uses the EPA WaterSense figure of about 300 gallons a day for an average American family at home. More free tools.

Planning a real site? We can animate it for your investors or permit hearing. See the studio · Start a project

How to Use It

Enter the IT load, the site's water usage effectiveness and average utilization. The calculator estimates on-site cooling water per day and per year, with a household comparison for context.

How This Calculator Works

The calculator runs these formulas in your browser:

Default assumptions and sources

WUE is The Green Grid's water usage effectiveness metric (site water ÷ IT energy); see the LBNL page on the Green Grid WUE paper. The household figure uses EPA WaterSense's estimate of about 300 gallons a day used at home by an average American family.

Worked example

A 50 MW IT load at 80% average utilization uses 50,000 × 24 × 0.8 = 960,000 kWh a day. At a WUE of 0.5 L/kWh that is 480,000 liters, or about 126,800 gallons a day, roughly 46 million gallons a year and the daily home use of about 420 households.

Limits

It counts water used on site for cooling and humidity only, not the water used to make the electricity. WUE changes with the weather, so a yearly average hides summer peaks; size water supply from the cooling designer's peak-day number.

Common Questions

What WUE should I use?

Closed-loop and dry-cooled designs can be near zero. Evaporative systems in hot, dry places can use far more. If you do not know, try a few values to see the range.

Does this include water for power generation?

No. It counts water used at the site. Power plants that use water for cooling add an indirect footprint on top.

Why does utilization matter?

Cooling water tracks heat, and heat tracks how hard the servers work. A site at 50% utilization rejects roughly half the heat of one running flat out.